Heat pump system sizing — water volume, expansion vessel and hot water cylinder

Heat pump

1 · Minimum water volume

AUX asks for at least 40 L of water in the system, not counting the water inside the unit. Count only the part that is always open — with every zone valve and TRV that can close, closed.

2 · Expansion vessel

The unit has a built-in 5 L vessel, 1.0 bar pre-charge. Check whether the whole system needs more.

3 · Hot water cylinder

Figures from the AUX R290 Installation & Commissioning Manual (sections 2.6, 2.7 and 9.4.2). The expansion vessel uses the standard sizing formula for water; for glycol systems use the vessel maker's data, as glycol expands more.